Faulty Transformer Repairing Services
A transformer is an electrical device used for energy transformation by electromagnetic induction between two or more circuits. Like all electronic devices, faults also happen in the transformer, which causes failures. One failure can cause many problems. A simple fault at the distributing end can cause failures. One failure can cause many problems. A simple fault at distributing end can cause a blackout of power to the whole area. The fault can also be very dangerous as the transformer contain a large quantity of oil in direct contact with high-voltage components. This increases the risk of fire and explosions due to failures. Different faults are caused by different reasons, impacting the power system differently.
- Minor repairs to faulty distribution transformer constitute replacement of one limb/bushing of the transformer, attending to loose contact /filtering of oil etc.
- Major repairs to faulty distribution transformer constitute of all required accessories such as HT, LT, coils, bushing lamination (CRGO)reconditioning tank, filling oil (after filtering), improving insulation level and repaired transformer shall fully be tested by meters and testing division and the tested transformers before releasing to the customer.
Transformer Repair Process
- Collection of the transformer from the client
- Store Registration
Faulty Transformer inspection
Six key steps to be applied
- Physical inspection
- General inspection, a report jointly signed with client representatives
Production &Assemble line
- Detect faulty as per inspection report
- Repairing process
- Replace damaged parts
- Drying cores for 48hrs
- Oil refill or filtering
- Assemble
Production assemble line
Six key tests to be applied
- Physical appearance inspection
- Test report of repaired transformers to be generated
Release
- Registration with store data
- Prepare delivery note
- Arrange logistics to deliver back to the client
Transformer Lifecycle Management Service
As with every other technical system, transformers are subjected to a certain amount of wear during operation. Yocean TLM covers a wide range of services to significantly lengthen the operation time of your transformers and, therefore, optimize utilization over the entire operation time:
- Condition assessment and diagnostics
- Online monitoring
- Consulting and expertise
- Maintenance and lifecycle extension
- Spare parts and accessories
- Repair and retrofit
Technical Specification
- Power: 30-31500kVA
- Voltage level: 10/0.4kV,20/0.4kV,35/10.5kV
- Frequency: 50/60Hv
- Number of phases: three-phase or single phase
- Tap changing methods: Off-circuit or no-load tap change
- Tapping range: ±5% or 2*2.5% or according to users requirements
- Connection Symbol: Yyn0 or Dynll or according to clients’ requirements
- Short circuit impedance: 4% or 6% or according to the client’s requirements
Oil-Immersed Transformer
Technical parameter of S-50-2500/35 Series low-loss distribution transformer
Type | HV | LV | Po kW | Pk750C kW | I o% |
S-50/35 | 35±5% or 35±2*2.5% | 0.4 | 0.17 | 1.15 | 1.8 |
S-100/35 | 0.24 | 1.92 | 1.8 | ||
S-150/35 | 0.28 | 2.27 | 1.6 | ||
S-160/35 | 0.29 | 2.26 | 1.6 | ||
S-200/35 | 0.35 | 3.17 | 1.4 | ||
S-250/35 | 0.41 | 3.77 | 1.4 | ||
S-315/35 | 0.49 | 4.54 | 1.4 | ||
S-400/35 | 0.59 | 5.48 | 1.2 | ||
S-500/35 | 0.69 | 6.59 | 1.2 | ||
S-630/35 | 0.84 | 7.87 | 1 | ||
S-800-35 | 0.99 | 9.41 | 1 | ||
S1000/35 | 1.16 | 11.55 | 0.8 | ||
S-1250/35 | 1.41 | 13.94 | 0.8 | ||
S-1600/35 | 1.7 | 16.68 | 0.7 | ||
S-2000/35 | 2.18 | 18.39 | 0.6 | ||
S-2500/35 | 2.58 | 19.67 | 0.5 |
Technical parameter of S-800~ 31500/35 Series low-loss transformer
Type | HV | LV | Po kW | Pk750C kW | I o% |
S-800/35 | 35±5% or 38± 5% | 3.15 6.3 10.5 | 0.17 | 1.15 | 1.8 |
S-1000/35 | 0.24 | 1.92 | 1.8 | ||
S-1250/35 | 0.28 | 2.27 | 1.6 | ||
S-1600/35 | 0.29 | 2.26 | 1.6 | ||
S-2000/35 | 0.35 | 3.17 | 1.4 | ||
S-2500/35 | 0.41 | 3.77 | 1.4 | ||
S-3150/35 | 0.49 | 4.54 | 1.4 | ||
S-4000/35 | 0.59 | 5.48 | 1.2 | ||
S-5000/35 | 0.69 | 6.59 | 1.2 | ||
S-6300/35 | 0.84 | 7.87 | 1 | ||
S-8000-35 | 35±2*2.5% or 38.5± 2*2.5% | 3.15 3.3 6.3 6.3 6.6 10.5 11 | 0.99 | 9.41 | 1 |
S10000/35 | 1.16 | 11.55 | 0.8 | ||
S-12500/35 | 1.41 | 13.94 | 0.8 | ||
S-16000/35 | 1.7 | 16.68 | 0.7 | ||
S-20000/35 | 2.18 | 18.39 | 0.6 | ||
S-25000/35 | 2.58 | 19.67 | 0.5 | ||
S-31500/35 |
Amorphous Alloy core Type Transformer
Characteristics of Amorphous Alloy Core
Amorphous alloy is extremely thin. Only 0.03m thick permeability magnetic material. It is a new high-technology product with sheets made from molten steel, adopting ultra-paid cooling technology through a cooling drum. Iron core made of amorphous alloy has advantages of high saturation magnetic induction strength, low coercivity, low equivalent to silicon steel sheet 1/3NI/5, low exciting current, anticorrosion, good temperature stability and long service life. Amorphous alloy transformer, whose core material is made of amorphous metal, is a new energy-saving product. Compared with silicon steel transformers, the core of the amorphous alloy distribution transformer reduces over 70% iron loss during no-load loss. Extensive use is of great importance to energy conservation and environmental protection. The domestic demand of 10kVA. Manufacturing. If we all use the amorphous alloy annually, which can ease the intense supply situation in our country. At the same time, saving electric charge of power using units can improve iron g term economic benefits, promote strength during the market competition and development and technological advancement of our country’s transformer manufacturing industry.
Product Introduction
ZGSII Series combined type transformer is a new distribution equipment (commonly known as the American box substation). HV load witch, insert the fuse, and HV limiting current limiting fuse are installed in the transformer tank, with mineral oil for insulation and cooling. Its advantages include reasonable and compact structure, snail dimension, flexible installation, convenient operation, small occupation area, etc. The combined transformer is especially suitable for the load center of the city power grid, reducing the loss and improving the quality of the power supply. The combined transformer has widely been used for urban power networks in many developed countries. Currently, our country is reforming the urban and rural power grids. ZGSII series combined type transformer is undoubtedly the best distribution equipment for urban power networks.
Combined Transformer Series
Product Features
Small dimension, reasonable and compact structure, hermetically sealed tank, fully insulated design, safe and reliable operation, strong overloading ability to withstand sudden short circuit ring network and terminal power supply can be used. Convenient operation, reliable power supply saving energy, low loss, loss S is not higher than the new value excellent impact resistance performance. The cable terminals, which can switch on and off the circuit on load with a current up to 200A, have long mechanical and electrical laments.
Main Technical Parameters
Hv Load Switch Parameters
No. | Item | The second position | The fourth position |
1. | Rated current | 300A | 300A |
2. | Max. working voltage | 15kV | 15kV |
3. | Lightening impulse level | 95kV | 95kV |
4. | Power frequently withstands voltage in 1min | 42kV,45kV(broken) | 42kV,45kV(broken) |
5. | Rated breaking current | 300A | 300A |
6. | Short time withstand current | 16kA | 12.5kA |
7. | Rated short circuit opening and closing times | 40kA | 31.5kA |
8. | Max. operation torque | <40N.m | <40N.m |
9. | Mechanical life | 2000times | 2000times |
10. | Rated current breaking current | 200times | 200times |
11. | Continuous working current | 300A | 300A |
HV Cable terminal parameters
No. | Item | The second position | The fourth position |
1. | Rated current | Kv | 12 |
2. | Rated current | A | 200,600 |
3. | Power frequently withstands voltage in 1min | kV | 42 |
4. | Insulation Resistance | MΩ | 2000 |
5. | Contacting resistance of contractor | uΩ | 100 |
Fuse Parameters
Rated power kVA Rated Voltage 60kV Rated voltage 10kV
| Current Limiting Fuse | Plug-in fuse type | Current Limiting Fuse | Plug–in fuse type |
100 | 50 | C08 | 40 | C06 |
160 | 80 | C10 | 50 | C08 |
200 | 80 | C10 | 80 | C10 |
250 | 125 | C10 | 80 | C10 |
315 | 150 | C12 | 80 | C10 |
400 | 150 | C12 | 100 | C11 |
500 | 175 | C14 | 125 | C12 |
630 | 175 | C14 | 150 | C12 |
800 | 200 | C16 | 150 | C14 |
1000 | 200 | C16 | 200 | C16 |
Transformer Parameter
Rated Power kVA | HvkV | Tapping Range | LVkV | Vector Group | PoW | Ok75oCkW | Io% | Uk% |
100 |
|
|
0.4 |
Dyn11 | 200 | 1500 | 1.3 |
4 |
160 |
|
| 290 | 2200 | 1.2 | |||
200 |
|
| 330 | 2600 | 1.1 | |||
250 |
|
| 400 | 3050 | 1.1 | |||
315 | 10 |
| 480 | 3650 | 0.9 | |||
400 | 10.5 | ±5% or 2*2.5% | 570 | 4300 | 0.9 | |||
500 | 11 |
| 680 | 5150 | 0.9 | |||
630 |
|
| 810 | 6200 | 0.8 |
4.5 | ||
800 |
|
| 980 | 7500 | 0.7 | |||
1000 |
|
| 10300 | 10300 | 0.6 |